H05-07V-K

FEATURES:
1 – Multiple-wire copper conductor
2 – PVC Insulated

PLACES OF USE
It can be used in buildings, dry places, connection and distribution plants, within pipes, under and above surface coats with or without cable straps.

TECHNICAL SPECIFICATIONS

Allowed operative temperature
Allowed short-circuit temperature
Nominal voltage
Test voltage
:70 °C
:160 °C (For max. 5 sec.)
: Uo/U – 300/500W
: 2 kW – 2.5 kW (AC)

 

Size Weights Electrical Specifications
Current-Carrying Capacity
Nominal Section Outer Diameter (~) Net Weight (~) Standard Delivery Length Standard Wrapping Brand Type Conductor DC. Resistance 20° (max.) Soil 20° (max.) Air 30° (max.)
mm² mm Kg/Km m cm ohm/km A A
1.50 3.00 20 100 Coil 3.3 15 24
2.50 3.80 35 100 Coil 7.98 20 32
4.00 4.50 50 100 Coil 4.95 25 42
6.00 5.00 75 100 Coil 3.3 33 54
10 6.50 125 100 Coil 1.91 45 73
16 7.80 180 100 Coil 1.21 61 98
25 10.0 280 100 Coil 0.780 83 129
35 11.0 380 100 Coil 0.554 103 158