NVV


FEATURES:
1 – Copper Conductor
2 – PVC Insulated
3 – Joint Sheathed
4 – PVC Sheathed

PLACES OF USE
In or outside of buildings, in cable channels, beneath the ground, in power plants, in switch and industry plants, in local power distribution, places where there is no mechanical damage, and in salt- and freshwater if produced specially.

TECHNICAL SPECIFICATIONS

Allowed operative temperature
Allowed short-circuit temperature
Nominal voltage
Test voltage
:70 °C
:160 °C (For max. 5 sec.)
: Uo/U – 300/500W
: 2 kW – 2.5 kW (AC)

 

Size Weights Electrical Specifications
Current-Carrying Capacity
Nominal Section Outer Diameter (~) Net Weight (~) Standard Delivery Length Standard Wrapping Brand Type Conductor DC. Resistance 20° (max.) Soil 20° (max.) Air 30° (max.)
mm² mm Kg/Km m cm ohm/km A A
2×1.50 11.00 170 1000 81 12.1 32 20
2×2.50 12.50 220 1000 81 7.41 42 27
2×4.00 14.00 280 1000 101 4.61 54 37
2×6.00 15.00 350 1000 101 3.08 68 48
2×10 17.00 470 1000 101 1.83 90 66
2×16 20.00 690 1000 121 1.15 116 89
2×25 23.00 1020 1000 141 0.727 150 118
3×1.50 12.00 190 1000 81 12.1 26 18.50
3×2.50 13.00 250 1000 81 7.41 34 25
3×6.00 16.00 420 1000 101 3.08 56 43
3×10 17.50 580 1000 121 1.83 75 60
3×16 21.00 870 1000 121 1.15 98 80
4×1.50 13.00 220 1000 81 12.1 26 18.5
4×2.50 14.00 300 1000 101 7.41 34 25
4×4.00 16.00 400 1000 101 4.61 44 34
4×6.00 17.00 500 1000 101 3.08 56 43
4×10 19.00 700 1000 121 1.83 75 60
4×16 23.00 1070 1000 141 1.15 98 80
4×25 28.00 1610 1000 141 0.727 128 106